Skip to content Skip to footer
This diesel generator set is engineered for
applications requiring reliable standby or prime
power in fixed installations.
It is designed with a focus on power continuity,
operational safety, and optimized fuel efficiency,
ensuring stable and consistent performance across
varying load conditions.
almpe900

Standby

900 kVA

Prıme

800 kVA

Fuel Type

DIESEL

Frequency

50 Hz
Technical Specifications Unit Value
Generator Model ALMPE - 900
Engine Model Perkins / 4006-23TAG3A
Fuel Type Diesel
Frequency Hz 50
Voltage V 231 / 400
Power Factor CosØ 0.8
Engine Brand Perkins
Engine Model 4006-23TAG3A
Engine Tуpe 4 Stroke Diesel Engine
Number of Cylinders/ Configuration 6L
Total Displacement It 22,921
Bore x Stroke mm 160 x 190
Compression Ratio 13,6:1
Engine Speed / Frequency d/dk/Hz 1500/50
Engine Standby Power kWm 786
Engine Prime Power kWm 705
Aspiration System Turbocharged, Intercooler
Injection System Direct
Governor Type Electronic
Cooling System Water Cooled
Coolant Capacity lt 105
Cooling Air Flow m3/dk 780
Lubricating Oil Capacity lt 113,4
Electrical System VDC 24
Battery Capacity Adet x Ah 2 x 150
Charging Alternator Output A 55
Jacket Water Heater Adet x W 1 x 2000
Combustion Air Flow m3/dk 71
Exhaust Gas Flow m3/dk 180
Exhaust Gas Temperature ºC 430
Fuel Consumption at 100% Load lt/s 172
Fuel Consumption at 75% Load lt/s 130
Fuel Consumption at 50% Load lt/s 90
Number of Phase / Poles 3/4
Excitation System Self Excited
Voltage Regulator Automatic
Voltage Regulation 1%
Insulation Class H
Protection Class IP23
Connection Type Star
Frequency Hz 50
Power Factor Cosø 0,8
Total Harmonic Distortion (No Load)
Output Voltage VAC 231 / 400

Details

Car ID: ALMPE 900 Manufacturer: 401 - 900 kVA Transmission: Prime
800 kVA
Fuel: Stand-by
900 kVA
Engine: Perkins Mileage: 50 Hz Jeneratör Modeli: ALMPE10

Contacts

Car's agent
Contact admin